What is Windage loss in Cooling Tower System?

Answer: Windage (or drift) losses (W) are the amount of total tower water flow that is evaporated into the atmosphere. From large-scale industrial cooling towers, in the absence of manufacturer’s data, it may be assumed to be:

W = 0.3 to 1.0 percent of C for a natural draft cooling tower without windage drift eliminators
W = 0.1 to 0.3 percent of C for an induced draft cooling tower without windage drift eliminators
W = about 0.005 percent of C (or less) if the cooling tower has windage drift eliminators
W = about 0.0005 percent of C (or less) if the cooling tower has windage drift eliminators and uses sea water as make-up water.